Rockwell-automation 6000 PowerFlex Medium Voltage Variable Frequency D Manuale Utente Pagina 72

  • Scaricare
  • Aggiungi ai miei manuali
  • Stampa
  • Pagina
    / 98
  • Indice
  • SEGNALIBRI
  • Valutato. / 5. Basato su recensioni clienti
Vedere la pagina 71
72 Rockwell Automation Publication 6000-IN007A-EN-P - October 2014
Chapter 4 No-load Test
2. In the Switch Method Selection dialog, press or .
3. If you select , the:
drive must be set to Local Control
position switch must be set to Drive
bypass contactor must be ON
drive must not be running.
4. If you select , the:
drive must be set to Local Control
position switch must be set to Drive
drive must be running.
5. Press to confirm selection.
ATTENTION: If the conditions are incorrect, the following dialog appears.
Vedere la pagina 71
1 2 ... 67 68 69 70 71 72 73 74 75 76 77 ... 97 98

Commenti su questo manuale

Nessun commento