Publication 2098-RM003A-EN-P October 2001
2-60 Command Reference
Homing Abort Deceleration
Format: :aa0D7fddddddddcc<cr>
Parameter
Code:
0x0D7
Valid Function
Codes:
0x0 = Read Working Value
0x1 = Write Working Value
0x2 = Read Non-Volatile Value
0x3 = Write Non-Volatile and Working Values
0x4 = Copy Non-Volatile Value to Working Value
0x5 = Copy Working Value to Non-Volatile Value
0x6 = Read Default Value
0x7 = Copy Default Value to Non-Volatile and Working Values
0x8 = Read Minimum Value
0x9 = Read Maximum Value
Valid Exception
Codes:
0x03 = EEPROM Write Error
0x05 = Data Above Maximum
0x08 = Invalid Function Code
Data Fields: dddddddd Deceleration used to bring the motor to a stop when
a homing sequence is terminated with the Stop
Homing input, in units of counts/second/second.
Minimum
Value:
0x00000000
Maximum
Value:
0x7FFFFFFF
Default: 100,000