Rockwell-automation 1794-APBDPV1 FLEX I/O PROFIBUS Adapter User Manual Manuale Utente Pagina 111

  • Scaricare
  • Aggiungi ai miei manuali
  • Stampa
  • Pagina
    / 153
  • Indice
  • SEGNALIBRI
  • Valutato. / 5. Basato su recensioni clienti
Vedere la pagina 110
Publication 1794-UM064B-EN-P - May 2014
Apply FLEX I/O Modules 99
Once Rtotal is known, you must determine the actual cable resistance that can be
accommodated. This is the difference between Rtotal and the module internal
source and sense resistances: Rcable=440-273-10=157 Ω.
Rcable is used to determine the wiring length allowed between the module and
the transmitter:
Note, the 2 in the denominator of the equation is necessary to account for the
resistance of both cable conductors (signal source + and signal and return).
Chapter Summary
In this chapter you learned how to apply the FLEX I/O analog modules.
Cable_length =
157
2*0.1
= 785 m
Vedere la pagina 110
1 2 ... 106 107 108 109 110 111 112 113 114 115 116 ... 152 153

Commenti su questo manuale

Nessun commento