14 DC-Input/Relay-Output Combination Module
Publication 1762-IN018B-EN-P - July 2013
Output Specifications
Specification Value
Voltage Range 5…265V AC
5…125V DC
Commons per Module 6
Output Type 6-Form A (normally open)
Signal Delay Time On-delay: 10 mS (max) Off-delay: 10 mS (max)
Off Leakage Current 0 mA
On-state Current (Min.) 10 mA @ 5V DC
Continuous Current per Point See table on page 14.
Continuous Current per Module 8 A
Total Controlled Load 1440VA/Module max
Relay Contact Ratings
Volts (max.) Continuous
Amps per
Point (Max.)
Amperes
(1)
(1) Surge Suppression - Connecting surge suppressors across your external inductive load will extend the life of the relay
contacts. For additional details, refer to Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.
Voltamperes
Make Break Make Break
240V AC 2.5 A 7.5 A 0.75 A 1800VA 180VA
120V AC 15 A 1.5 A
125V DC 1.0 A
0.22 A
(2)
(2) For DC voltage applications, the make/break ampere rating for relay contacts can be determined by dividing 28 VA by the
applied DC voltage. For example, 28 VA/48V DC = 0.58A. For DC voltage applications less than 14V, the make/break rating
for relay contacts cannot exceed 2A.
28VA
(2)
24V DC 2.0 A 1.2 A
28VA
(2)