Rockwell-automation 1753-PCS-PAR Using RSLogix Guard PLUS! with GuardP Manuale Utente Pagina 112

  • Scaricare
  • Aggiungi ai miei manuali
  • Stampa
  • Pagina
    / 122
  • Indice
  • SEGNALIBRI
  • Valutato. / 5. Basato su recensioni clienti
Vedere la pagina 111
Publication 1753-PM001A-EN-P - November 2005
B-6 Configure the GuardPLC OPC Server
12. Drag DO1 from the Signal Editor to the DO[01].Value signal
field.
13. Close the DO Signal Connections window and the Signal Editor.
Set the System Properties
Controller
1. Right-click COM under the GuardPLC 1600 controller tree and
choose Properties.
2. Set the IP Address to 192.168.0.99 and click OK.
3. Right-click Programming Terminal and choose Properties.
4. Set the System ID (SRS) to 5. Click OK.
5. Right-click OPC-Server and choose Properties.
TIP
There are 3 devices in our system:
the PC running the Signal Editor,
the OPC Server, and
the GuardPLC controller.
All must have unique SRS numbers.
Vedere la pagina 111
1 2 ... 107 108 109 110 111 112 113 114 115 116 117 ... 121 122

Commenti su questo manuale

Nessun commento