8–5
Application Examples
Publication
17466.8 - April 1997
Channel Configuration
Configuration setup for current transducers:
channels 0, 1, and 2
4–20 mA input type
engineering units data format
zero data word in the event of an open circuit
10 Hz input filter to reject high frequency noise and provide
60 Hz line noise rejection
Configuration setup for pressure transducer:
channel 3
4–20 mA input type
engineering units data format
zero data word in the event of an open circuit
10 Hz input filter to reject high frequency noise and provide
60 Hz line noise rejection
Configuration setup for level sensor:
channel 4
0–10V dc input type
engineering units data format
zero data word in the event of an open circuit
10 Hz input filter to reject high frequency noise and provide
60 Hz line noise rejection