SLC 500™ Analog Input Module
19
Publication 1746-IN006A-US-P
Input Specifications
Description Specification
Type of Input (Selectable) ±10V dc
1 to 5V dc
0 to 5V dc
0 to 10V dc
0 to 20 mA
4 to 20 mA
±20 mA
0 to 1 mA
Type of Data (Selectable) Engineering Units
Scaled-for-PID
Proportional Counts (-32,768 to +32,767 range)
Proportional Counts (User Defined Range, Class 3 only)
1746-NI4 Data Format
Input Impedance 1 M
Ω
Voltage Input (maximum)
±
30V between any two signal terminals
Current Input (maximum) 30 mA
Time to Detect Open Circuit 1 module scan
Input Step Response
(1)
(1 )Depends on filter selected. Refer to the 1746-NI8 User Manual, publication 1746-6.8.
Input Resolution 1 mV or 1
µ
A
Display Resolution 1 mV or 1
µ
A
Overall Module Accuracy
(0
°
C to +60
°
C, +32
°
F to +140
°
F)
Voltage input types
(
±
10V dc, 1 to 5V dc, 0 to 5V dc, 0 to 10V dc):
±
0.1%
Current Input Types
(0 to 20 mA, 4 to 20 mA, ±20 mA):±0.05%
Current Input Type (0 to 1 mA): ±0.5%
Overall Module Drift Voltage input type: ±6 ppm/°C
Current Input Type: ±12 ppm/°C