Rockwell-automation 150 USE MN/SMC DIALOG + CONTROLLER Manuale Utente Pagina 14

  • Scaricare
  • Aggiungi ai miei manuali
  • Stampa
Vedere la pagina 13
1-4
Product Overview
Starting Modes (cont.)
Dual Ramp Start
This starting mode is useful on applications that have varying loads
(and therefore varying starting torque requirements). Dual Ramp
Start allows the user to select between two separate Soft Start profiles
with separately adjustable ramp times and initial torque settings.
Figure 1.4 Dual Ramp Start
Full Voltage Start
This starting mode is used for applications requiring across-the-line
starting. The output voltage to the motor will reach full voltage
within 1/4 second.
Figure 1.5 Full Voltage Start
Dual Ramp Start is available only with the standard controller.
Percent
Voltage
Initial
Torque #1
100%
Start #1 Run #1
Ramp #2
Ramp #1
Start #2
Time (seconds)
Run #2
Initial
Torque #2
100%
Percent
Voltage
Time (seconds)