Rockwell-automation 150 USE MN/SMC DIALOG + CONTROLLER Manuale Utente Pagina 106

  • Scaricare
  • Aggiungi ai miei manuali
  • Stampa
Vedere la pagina 105
7-22
Options
Figure 7.18 Typical Retrofit Wiring Diagram for the Slow Speed with Braking
Option
Customer supplied.
Overload protection should be disabled in the SMC Dialog Plus controller.
Refer to the controller nameplate to verify the rating of the control power input voltage.
Note: Refer to Chapter 3 for typical power circuits.
Brake
OL
➀ ➁
Stop
M
Control Power
Slow Speed
Start
11 12
13 14 15 16 17 18 19 20
21 22
23 24 25 26 27 28 29 30
Internal
Auxiliary
Contacts
Auxiliary contacts set
for Normal
SMC Dialog Plus
Control Terminals
Vedere la pagina 105
1 2 ... 101 102 103 104 105 106 107 108 109 110 111 ... 188 189

Commenti su questo manuale

Nessun commento