Rockwell-automation T8013 Trusted SOE and Process Historian Package Manuale Utente Pagina 27

  • Scaricare
  • Aggiungi ai miei manuali
  • Stampa
  • Pagina
    / 28
  • Indice
  • SEGNALIBRI
  • Valutato. / 5. Basato su recensioni clienti
Vedere la pagina 26
Trusted
TM
SOE and Process Historian Package T8013
Issue 16 April 2010 PD-T8013 27
5. SOE and Initial States
The following should be noted when using SOE data collection by any method.
Native output modules (P8451,61,71 etc.) never record the initial state of an output as an
SOE event.
Non-native output modules (e.g. Regent modules) record an initial state of TRUE as an SOE
event.
All inputs supporting SOE will always record an event if the initial input state is TRUE.
No SOE is recorded if a variable is locked, either input or output.
At an MP handover, Regent outputs, Peer to Peer outputs, MP complex equipment definition
board TTMRP_2 and SOE board points that are TRUE at an MP handover will generate an
SOE event.
Vedere la pagina 26
1 2 ... 22 23 24 25 26 27 28

Commenti su questo manuale

Nessun commento