Rockwell-automation T7411F ICS Regent+Plus Monitored Digital input Mod Manuale Utente Pagina 12

  • Scaricare
  • Aggiungi ai miei manuali
  • Stampa
  • Pagina
    / 24
  • Indice
  • SEGNALIBRI
  • Valutato. / 5. Basato su recensioni clienti
Vedere la pagina 11
Monitored Digital Input Modules
, Type F (T7411F, T7418F)
12
Industrial Control Services
Figure
7
shows a single switch connected to a redundant
monitored input modules. This type of configuration
uses a
line monitor device which contains two zener diodes, one in
series with the field switch and one in parallel with the field
switch.
Figure
7
. Line Monitoring, Single Switch Connected to
Redundant Modules.
Vedere la pagina 11
1 2 ... 7 8 9 10 11 12 13 14 15 16 17 ... 23 24

Commenti su questo manuale

Nessun commento