Guarded Analog Output Modules
(T3480)
PD
-
6026
Mar
-
06
7
Application
Guarded analog output modules are suited for high integrity
control of analog output devices. Guarded output modules can
be used for fail
-
safe or fault tolerant operation.
Fail
-
Safe Configuration
As shown in Figure
3
, fail
-
safe configuration uses a single
Guarded module. I
n this configuration, the worst case failure
will cause the output to fail to the off state.
In a fail
-
safe configuration, a module failure and subsequent
removal of the module disables all of its outputs.
Figure
3
. Fail
-
Safe Configuration.
Fault Tolerant Configuration
For fault tolerant operation, two Guarded modules are
connected in parallel as shown in Figure
4
. In this
configuration, operation continues even if on
e module fails.
In the fault tolerant configuration, a failed module can be
removed and replaced without interrupting operation of the
loads.