RSView32 commands A–11
If both the /P parameter and the /Sn parameter are
specified, the prompt dialog box will display the
alarm severity at runtime, but the operator cannot
change the severity.
[/R] Logs the remark to a printer as well as to the alarm
log file. If the alarm severity is not specified (/Sn
parameter), the printer for Severity 1 is used. If no
printer is assigned to the specified severity, the alarm
log remark is not printed.
[/Ttagname] The string that is logged in the Tagname column of
the alarm log file. This string can be a tag name, the
name of a user–generated alarm event, or any other
string that matches the syntax of a tag name. You can
use this parameter to correlate remarks with specific
alarm transactions for generating reports later.
AlarmLogSend
ToODBC
AlarmLogSendToODBC <data_source> <target_table_name>
[/Wn] [/Uuser_name] [/Ppassword]
Exports alarm log data from DBF files to the ODBC database. The
connection to the ODBC database is maintained for the length of
time specified by the wait (/W) parameter.
<data_source> A valid ODBC data source name. If the name has a
space embedded in it, enclose the name in
quotes (“”).
<target_table_ The name of a table in the ODBC database where
name> the data will be exported. If the table does not exist
RSView32 attempts to create it.
[/Wn] The time the connection to the ODBC database will
be maintained. If nothing is specified, the wait time
defaults to about 5 minutes. A wait time of zero
keeps the connection open until the project is
stopped.