68 Publication 2711P-QS001A-EN-P - October 2007
Chapter 6 Review Unsupported Features and Implement Workarounds for Migration Issues
Replacing the Set Bit
Cursor Point Object
In PanelBuilder 1400e software, the set bit cursor point object was
available only on keypad terminals. FactoryTalk View ME software
provides an ActiveX control as an alternative to the set bit cursor point
object. To use this control, you must use a PanelView Plus CE
terminal. The ActiveX control must be registered on the terminal. The
open Windows CE environment of the PanelView Plus CE terminal
allows you to do this.
You must download, register, and configure the ActiveX control in
your FactoryTalk View ME application. See page 46 for the location of
these files.
Register the ActiveX Control on Your Computer
Follow these steps to register the ActiveX control for the set bit cursor
point object on your computer.
1. Extract the downloaded files
to a location on your hard
drive.
2. Open your migrated
application in FactoryTalk
View ME software.
TIP
The Migration Solutions.apa file contains a set bit cursor point
object display which you can test run to review how the object
works.