Controller logging Chapter 3
Example:
Retrieve the Execution Modification Count by using a GSV ladder instruction
The following rung of ladder logic shows how to set the Execution Modification
Count to a known value.
Example:
Ladder instruction to set the Execution Modification Count to a known value
You use a message instruction of message type CIP Generic and a service type of
Controller Log Config Execution Set to configure whether the Execution
Modification Count includes forces.
If it is sent a value of 1, forces are included in the counter. If it is sent a value of 0,
forces are not included.
The following rung of ladder logic shows how to send the message instruction,
followed by the configuration dialog box of the message instruction.
Rockwell Automation Publication 1756-PM015F-EN-P October 2014 33