Add a PowerFlex 70 Drive to an RSLogix 5000 Project Chapter 2
6. Change the O.CommandedFreq
tag to 15000 engineering units
(this is approximately 59.5 Hz).
7. Change the Start tag to 1.
The display on the drive registers
the speed increase in Hz until the
value entered at the reference tag
is reached.
8. Change the Start tag back to 0.
9. Change the Stop tag to 1.
The display on the drive will show
a speed decrease until the drive
reaches 0.00 Hz.
WARNING: If there is a motor attached to your drive, completing the next step will cause it to turn.