Publication GMLC-5.2 - November 1999
Using the Dedicated Discrete Inputs 689
The recommended ladder logic for homing axes is shown below. Only
axes 0 and 1 are shown, but axes 2 and 3 are handled in the same manner.
The Rack Address in the motion controller is set to 5 and the Starting
Group parameter to 0. Thus the dedicated discrete RIO bits appear in I/O
group 1 of rack 5 (I/O:051).
Program Listing Report PLC-5/30
Rung 2:1
| Home Axis 0 |
| Axis 0 Selected |
| I:002 O:051 |
+----] [-----------------------------------------------------( )-----+
|01 00 |
Rung 2:2
| Home Axis 1 |
| Axis 1 Selected |
| I:002 O:051 |
+----] [-----------------------------------------------------( )-----+
|02 01 |
Rung 2:3
| Home |
| Axis 0 Selected |
| Selected Axes |
| O:051 O:051 |
+-+---] [----+-----------------------------------------------( )-----+
|| 00 | 10 |
| |Axis 1 | |
| |Selected | |
| | O:051 | |
| +---] [----+ |
|01 |
!
ATTENTION:
Do not use the PLC ladder logic shown here
for homing axes in the same PLC program with the ladder
logic shown later for jogging axes or improper operation can
result.
Vedere la pagina 725