Rockwell-automation AutoMax R-Net Processor Module Manuale Utente Pagina 18

  • Scaricare
  • Aggiungi ai miei manuali
  • Stampa
Vedere la pagina 17
4Ć2
Register Function
0 Reserved for System Use
1 Reserved for System Use
2 Reserved for System Use
3 Reserved for System Use
4 Drops On Line Status Bit 15Ć0
5 Drops On Line Status Bit 31Ć16
6 Drops On Line Status Bit 47Ć32
7 Drops On Line Status Bit 63Ć48
8 Reserved for System Use
9 Reserved for System Use
10 Reserved for System Use
11 Reserved for System Use
12 Node Number
13 Slot Number
14 Messages Received Count
15 Receive Timeouts Count
16 CRC Error Count
17 Overrun Error Count
18 Illegal Message Count
19 Messages Transmitted Count
20 Lost Token Count
21 Maximum Node Number
22 Response Timeout in Seconds
23 Current Token Time
24 Maximum Token Time
25 Reserved for System Use
:
49 Reserved for System Use
50 Transmit Global Data Enabling Register for AutoMate Image Register 71
51 Transmit Global Data Enabling Register for AutoMate Image Register 72
52 Transmit Global Data Enabling Register for AutoMate Image Register 73
53 Transmit Global Data Enabling Register for AutoMate Image Register 74
54 Reserved for System Use
:
59 Reserved for System Use
60 LED Error Code
61 Reserved for System Use
62 Reserved for System Use
63 Reserved for System Use
Figure 4.2Ć Status and Control Registers
4.1.1.1 Registers4Ć7(Drops On Line Status)
Registers4Ć7indicate which drops are active on the RĆNet network.
This register will display only up to node 63; nodes 64Ć250 cannot be
displayed.
4.1.1.2 Register 12 (Node Number)
The value of the node number switch settings (0Ć250) on the module
faceplate is stored in this register. The onĆboard CPU reads the value
of the switch settings only at powerĆup.