3) Select the Network tab and enter the values; the default recommended values:
Connect TimeOut = 1000
BindResp Timeout = 1200
MaxAge = 2500
BindReqTimeout = 1000
Update Timeout = 60000
Configure Bindings
You need to set up data links between resources to create binding variables. You can
link resources from the Internal Bindings List Window or set up a link between
resources from the Link Architecture view.
1) Select the Link Architecture View.
2) Select the data link button on Resource 1 and extend the data line to the data
link button on Resource 2.
3) Repeat this for Resource 2 to Resource 1.