Addressing syntax for Allen–Bradley programmable controllers D–13
In RSView32, the first physical module of each type (input or output)
is address slot number 0. The next module of the same type in the
next higher–numbered rack slot is address slot number 1, and so on.
Example: SLC 5 I/O module addressing
SLC
Type
Rack
Configuration
CV for MS-DOS
®
Address or
APS Address
RSView32
Address
Fixed
L40
I/O module slot 0
(fixed)
I:0.0 or I:0
I:0.1
O:0
I:0.0 or I:0
I:0.1 or I:1
O:0
I module slot 2 I:2 I:2
Fixed
L30
I/O module slot 0
(fixed)
I:0.0 or I:0
I:0.1
O:0
I:0.0 or I:0
I:0.1 or I:1
O:0
I module slot 1 I:1 I:2
O module slot 2 O:2 O:1
Fixed
L20
I/O module slot 0
(fixed)
I:0.0 or I:0
O:0
I:0.0 or I:0
O:0
I module slot 1 I:1 I:1
I module slot 2 I:2 I:2
Modula
r
CPU slot 0 N/A N/A
O module slot 1 O:1 O:0
I module slot 2 I:2 I:0
O module slot 3 O:3 O:1
Vedere la pagina 710