Rockwell-automation 61C345 4 Input 4-20mA Analog Rail Module Manuale Utente Pagina 18

  • Scaricare
  • Aggiungi ai miei manuali
  • Stampa
Vedere la pagina 17
3Ć4






0 1
2
3
IĆIN
Common
(no label)
4Ć20mA+ input
common
(shield; no connection)*
1 4
5
6
IĆIN
Common
(no label)
4Ć20mA+ input
common
(shield; no connection)*
2 7
8
9
IĆIN
Common
(no label)
4Ć20mA+ input
common
(shield; no connection)*
3 10
11
12
IĆIN
Common
(no label)
4Ć20mA+ input
common
(shield; no connection)*
*This terminal makes no electrical connection to the Analog Rail printed circuit
board.
Step 10. For each of the four input channels, connect a shield wire
from the external hardware to the third terminal (terminals
3, 6, 9 and 12, respectively) on each channel. The shield
wire at the external hardware end of the cable should be
connected to the source reference point. See figure 3.2.
Vedere la pagina 17
1 2 ... 13 14 15 16 17 18 19 20 21 22 23 ... 47 48

Commenti su questo manuale

Nessun commento