Publication 20D-UM002C-EN-P - November 2003
Communicating with Devices on a DeviceNet Link 8-3
Step 2: Configure the daughtercard as part of the system
Use RSLogix 5000 programming software to map the 1788-DNBO card as
part of the DriveLogix system. In the Controller Organizer, add the card to the
I/O Configuration folder.
Complete your system configuration and develop your program logic. Then
download the project to the controller.
1. In RSLogix 5000 programming software, select the I/O Configuration folder.
2 Right-click to select New Module and add a 1788-DNBO communication daughtercard.
4. Specify slot number 1 for the communication card.
Vedere la pagina 182