Publication 2711-UM014G-EN-P - September 2008 69
Applying Power and Resetting Terminal Chapter 2
Press this function key on To set this RIO
parameter
Description Options
550/600 900/1000/1400
F1 Rack # Rack address of terminal on RIO network.
On PV550/600: Press ↵ to open the
scratchpad. Enter the rack address and
press ↵ again.
On PV900/PV1000/PV1400: Press F1 to
set the rack #, then use the up and down
arrow keys to select an address.
0…76
F1 F2 Rack Size Rack size of terminal. Each key press
displays a different size. The terminal
occupies a single rack.
1/4, 1/2, 3/4, Full
F2 F3 Starting Module Group Starting module group number of the
terminal in the assigned rack. Each key
press displays a different module group.
0,1 2,3 4,5 6,7
F3 F4 Pass-through Enabled Enables or Disables Pass-through, which
lets you transfer applications between a
computer on a DH+ link and a terminal on
a remote I/O link. A PLC-5 controller
passes data between the networks.
Yes or No
F4 F5 Last Chassis Specifies whether the terminal occupies
the last module group in the assigned
rack (applies only to PLC2 controllers).
Yes or No
F5 Block Transfer Timeout Timeout value for block transfers. Each
key press toggles a value.
0…60 seconds
(0 is the default)
F6 F6 Baud Rate Communication rate at which the
terminal will communicate on the RIO
network.
BaudMax. Cable Length
57.6K 10,000 ft
115.2K 5,000 ft
230.4K 2,500 ft