Rockwell-automation 2707-NP2 MICROVIEW SOFTWARE PROGRAMMING MANUAL Manuale Utente Pagina 90

  • Scaricare
  • Aggiungi ai miei manuali
  • Stampa
  • Pagina
    / 134
  • Indice
  • SEGNALIBRI
  • Valutato. / 5. Basato su recensioni clienti
Vedere la pagina 89
Publication 2707-PM002B-EN-P
12-12 Entering MicroView Configuration Data
Advisor Update Rate
Selecting Advisor Update Rate from the PLC Hardware Parameters
Option Selection menu, displays the following:
The Advisor Update Rate is the periodic rate at which the MicroView
scans the Advisor register. For example a rate of 2.00 means the
MicroView reads the advisor register once every 2 seconds.
To assign a new Advisor Update Rate, enter a valid decimal number
and press [Return]. The valid range is from 1 to 12.5 seconds. The
default is 2 seconds. Entries are rounded up to the next higher 0.1
second.
To save the new Advisor Update Rate, press [Esc]. You are returned to
the PLC Hardware Parameter - Option Selection menu.
Note: Because the advisor adds to the network communication
traffic, the rate should be set to the highest possible value that is
acceptable for your application.
Vedere la pagina 89
1 2 ... 85 86 87 88 89 90 91 92 93 94 95 ... 133 134

Commenti su questo manuale

Nessun commento