Chapter
5–1
Selecting Options
This chapter describes DIP switch location and functions on the Bulletin
2705 RediPANEL Keypad Module. It also lists the switch bank settings for
selecting function and configuration options.
See Figure 5.1 to identify the Keypad Module switch banks.
Figure 5.1
Switch Bank Location and Functions on Bulletin 2705 Keypad Module
Switch bank #1 (SW–1) sets the rack address.
Switch bank #2 (SW–2) controls format and communication parameters:
baud rate, data format, and the modes for Destination Bits, Last Rack,
Keyswitch, Handshake and Last State.
Switch bank #3 (SW–3) establishes rack size and the modes for Stored
Message Display, Split Display and Keyboard type.
IMPORTANT NOTE: Remove power from the module before setting DIP
switches. Switch settings are scanned only on power–up.
Chapter Objectives
DIP Switches