8 DC Link Fuse Upgrade Kit for RGU in Parallel with NRU
Wiring the New Circuit
Important:Use the enclosed stranded 14 gage wire (Belden 30614 or
equivalent). Use the red wire for 115Vac signals and the white
wire for 115Vac neutral. Use the enclosed wire tags.
1. Connect the normally closed Microswitch contacts (contacts that open
when the fuses blow) on the fuses in series with the new relay coil
(CR5). The normally closed contact is between terminal 1 and 2 on each
Mircroswitch. Figure 7
defines the terminals on the Microswitch. Figure
8 illustrates the contacts inside the Microswitch. Refer to Figure 9 for
RGUs with two fuses. Refer to Figure 10
for RGUs with four fuses.
Figure 7 Microswitch Terminals
Figure 8 Microswitch Contacts