Rockwell-automation 1794-OF8IH FLEX Isolated Input/Output HART Analog Manuale Utente Pagina 94

  • Scaricare
  • Aggiungi ai miei manuali
  • Stampa
  • Pagina
    / 164
  • Indice
  • SEGNALIBRI
  • Valutato. / 5. Basato su recensioni clienti
Vedere la pagina 93
Publication 1794-UM065B-EN-E - September 2010
82 Configure Module Messaging
Get Device Info Block 1 Message
Get Device Information Block 1 Message – Request Packet Structure
Field Value Definition
Message Type "CIP Generic"
Service Type Get Attribute Single Read From Module
Service Code 0x0E
Class Name 0x7D FLEX Module Object
Instance 1…8 (Module next to Adapter = 1) Module Location
Object Attribute 0x87 = Channel 0 (Add 4 for next channel)
0x8B = Channel 1
0x8F = Channel 2
0x93 = Channel 3
0x97 = Channel 4
0x9B = Channel 5
0x9F = Channel 6
0xA3 = Channel 7
Selects Channel that the
data is from
Reply Size 48 bytes
Request Size 0
Get Device Information Block 1 Message – Reply Packet Structure
Offset
(1)
Field Value Definition
0 Status 00 = SUCCESS
0x86 = Channel is not
HART Enabled
0x87 = No Device Found
Command status
1 Echo of Channel 0…7 Channel
2 HART ManufacturerIDCode (1 byte) CMD#0, Byte 1
3 HARTDeviceTypeCode (1 byte) CMD#0, Byte 2
4 HARTUnivCmdCode (1 byte) CMD#0, Byte 4
5 HARTTransSpecRev (1 byte) CMD#0, Byte 5
6 HARTSoftwareRevision (1 byte) CMD#0, Byte 6
7 HARTHardwareRevision (1 byte) CMD#0, Byte 7
8…11 HARTDeviceIDNumber (4 bytes - UINT) CMD#0, Bytes
9…11
Bytes re-ordered
into Intel Format
(LSB 1st ) from HART
format (MSB 1st)
12…15 TagSize 8 (4 bytes)
16…23 TagString (8 bytes unpacked ASCII) CMD#13, Bytes
0…5
24…27 DescriptorSize 16 (4 bytes)
Vedere la pagina 93
1 2 ... 89 90 91 92 93 94 95 96 97 98 99 ... 163 164

Commenti su questo manuale

Nessun commento