Rockwell-automation 1794-OF8IH FLEX I/0 8 Isolated Output Analog Modul Manuale Utente Pagina 13

  • Scaricare
  • Aggiungi ai miei manuali
  • Stampa
  • Pagina
    / 28
  • Indice
  • SEGNALIBRI
  • Valutato. / 5. Basato su recensioni clienti
Vedere la pagina 12
FLEX I/O Isolated Output HART Analog Module 13
Publication
1794-IN120C-EN-P - April 2009
(1)
This alarm is disabled in Analog 0…20 mA formats (Formats 0,1,3) or if “Wire Fault Detection” is not
enabled in configuration.
Output Map
Word Bit
1514131211109876543210
0RG
R
RRRRRRD
G
7
D
G
6
D
G
5
D
G
4
D
G
3
D
G
2
D
G
1
D
G
0
1 Channel 0 Output Data
2 Channel 1 Output Data
3 Channel 2 Output Data
4 Channel 3 Output Data
5 Channel 4 Output Data
6 Channel 5 Output Data
7 Channel 6 Output Data
8 Channel 7 Output Data
DGn: Channel n Digital Output Data. Valid in Digital mode
only.
0: Output 0 mA
(1)
1: Output 22 mA
GR:
R
Global reset. Resets all latched wire fault alarms
Reserved
0: Inactive 1: Active
(1)
When Open Wire Detect is Enabled, 0 = 100 µA on Output
Vedere la pagina 12