Publication 1794-IN123B-EN-P - May 2009 4 PN-47876
Supersedes Publication 1794-IN123A-EN-P - July 2008 Copyright © 2009 Rockwell Automation, Inc. All rights reserved.
Specifications - Flex I/O 240V AC Output Module 1794-OM16
Attribute Value
Number of I/O channels 16, nonisolated
Module location Cat. No. 1794-TBN, 1794-TBNF
Output voltage 159V AC min @ 47...63 Hz
240V AC nom @ 47...63 Hz
264V DC max @ 47...63 Hz
On-state current 50 mA min per output, min
0.5 A per output, 4 A max per module
(2)
Surge current 7 A for 40 ms each, repeatable every 8 seconds
Off-state leakage, max 2.5 mA
Isolation voltage 250V (continuous), Basic Insulation Type
Type tested at 1706V DC for 60 s, between field side and system
No isolation between individual channels
Field Bus current 116 mA
Power dissipation, max 6 W @ 264V AC
Thermal dissipation, max 20.47 BTU/hr @ 264V AC
Indicators (field side) 16 yellow status indicators
Output signal delay
(1)
Off to On
On to Off
1/2 cycle max
1/2 cycle max
(1)
Delay time is the time from the receipt of an output on or off command to the output actually turning on or off.
(2)
If using 0.5 A outputs, alternate wiring so that no two 0.5 A outputs are next to each other.
ATTENTION
1794-OM16 module outputs are not fused. Fused outputs are recommended.
If not using a 1794-TBNF terminal base and fusing is required, external
fusing must be provided.
General Specifications
Attribute Value
Terminal base screw torque Determined by installed terminal base
Dimensions (with module installed)
H x W x D
94 x 94 x 91 mm
(3.7 x 3.7 x 3.6 in.)
External AC power supply voltage, nom 240V AC
External AC power voltage range 159...264V AC, 47...63 Hz
Terminal base load current, max 1794-OM16: 10 A
Pilot duty rating OM16: C300
North American temp code T4
Keyswitch position 8
Enclosure type rating None (open-style)
Wire size Determined by installed terminal base
Wiring category
(1)
(1)
Use this Conductor Category information for planning conductor routing. Refer to Industrial Automation Wiring and
Grounding Guidelines, publication 1770-4.1
.
2 - on signal ports
Environmental Specifications
Attribute Value
Operating temperature IEC 60068-2-1 (Test Ad, Operating Cold),
IEC 60068-2-2 (Test Bd, Operating Dry Heat),
IEC 60068-2-14 (Test Nb, Operating Thermal Shock):
0...55 °C (32…131 °F)
Storage temperature IEC 60068-2-1 (Test Ab, Unpackaged Non-operating Cold),
IEC 60068-2-2 (Test Bb, Unpackaged Non-operating Dry Heat),
IEC 60068-2-14 (Test Na, Unpackaged Non-operating Thermal Shock):
-40…85 °C (-40…185 °F)
Relative humidity IEC 60068-2-30 (Test Db, Unpackaged Damp Heat):
5…95% non-condensing
Vibration IEC60068-2-6 (Test Fc, Operating):
2 g @ 10...500 Hz
Shock IEC60068-2-27 (Test Ea, Unpackaged shock):
Operating 15 g
Non-operating 15 g
Emissions CISPR 11:
Group 1, Class A (with appropriate enclosure)
ESD immunity IEC 61000-4-2:
6kV contact discharges
8kV air discharges
Radiated RF immunity IEC 61000-4-3:
10V/m with 1 kHz sine-wave 80% AM from 80...2000 MHz
10V/m with 200 Hz 50% Pulse 100% AM at 900 MHz
10V/m with 200 Hz 50% Pulse 100% AM at 1890 MHz
1V/m with 1 kHz sine-wave 80% AM from 2000...2700 MHz
EFT/B immunity IEC 61000-4-4:
±2kV at 5 kHz on power ports
±2kV at 5 kHz on signal ports
Surge transient immunity IEC 61000-4-5:
±1kV line-line(DM) and ±2kV line-earth(CM) on power ports
±1kV line-line(DM) and ±2kV line-earth(CM) on signal ports
Conducted RF immunity IEC 61000-4-6:
10V rms with 1 kHz sine-wave 80% AM from 150 kHz…80 MHz
Damped oscillatory wave immunity ±1kV line-line(DM) and ±2.5kV line-earth(CM) on signal ports
±1kV line-line(DM) and ±2.5kV line-earth(CM) on power ports
Certifications
Certifications (when product is
marked)
(1)
Value
c-UL-us UL Listed Industrial Control Equipment, certified for US and Canada. See
UL File E65584.
UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations,
certified for U.S. and Canada. See UL File E194810.
CE European Union 2004/108/EC EMC Directive, compliant with:
EN 61326-1; Meas./Control/Lab., Industrial Requirements
EN 61000-6-2; Industrial Immunity
EN 61000-6-4; Industrial Emissions
EN 61131-2; Programmable Controllers (Clause 8, Zone A & B)
European Union 2006/95/EC LVD, compliant with:
EN 61131-2; Programmable Controllers (Clause 11)
C-Tick Australian Radiocommunications Act, compliant with:
AS/NZS CISPR 11; Industrial Emissions
(1)
See the Product Certification link at www.ab.com for Declarations of Conformity, Certificates, and other certification
details.