FLEX I/O DC Input, Output, and Input/Output Analog Modules 7
Publication 1794-IN106D-EN-E - January 2014
Connect Wiring
Connect the wiring for the 1794-TB3G and 1794-TB3GS terminal bases as shown in the
following figure:
Terminal Base Wiring for the 1794-IE12/A Analog Input Module
ATTENTION: To reduce susceptibility to noise, power analog modules and
digital modules from separate power supplies. Do not exceed a length of
10 m (33 ft) for DC power or analog I/O cabling.
ATTENTION: Do not daisy-chain power or ground from this terminal base
unit to any AC or DC digital module terminal base units.
ATTENTION: Do not exceed a length of 10 m (33 ft) for signal cabling.
I = Current [1794-TB3G shown]
V=Voltage
C-0...C-11 = Returns for I or V connections 0...11
+24V DC = Terminals C-34 and C-50
COM = Terminals C-35 and C-51
Chassis ground (CG) = Terminals B-16, B-33, C-38, C-40...C-45, C-47
NC = No connection
For daisy-chaining: Supply in – C-34 (+) and C-35 (-)
Supply out – C-50 (+) and C-51 (-)
24V DC
Supply In
24V DC
Supply Out
17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15
16
35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51
34
Chassis
Ground
Chassis
Ground
+V COM +V COM
Chassis Grounds for Shields
A
B
C
NC
I0 I1 I2 I3 I4 I5 I6 I7
I8 I9 I10 I11
V0 V1 V2 V3 V4 V5 V6 V7
V8 V9 V10 V11C0 C1 C2 C3 C4 C5 C6 C7
C8 C9 C10 C11NC
NC NC
Commenti su questo manuale