ArmorBlock MaXum 4 Output Module Series B 11
Publication 1792D-IN040B-EN-P - September 2000
Specifications
4 Output Module - Cat. No. 1792D-OB4D
Max. Min.
Outputs per block 4 sourcing outputs labeled 00, O1, O2, and O3
Output Auxiliary Voltage 30V 10V
On-state Voltage Drop 1V -
On-state Current 2A -
Off-state Leakage 1.5mA -
Module Current (all outputs) 4.0A -
Surge Current - for 10 ms,
repeatable every 2s
4.0A -
No Load Sense Current (On-state) 0.18A -
Indicators Net/Mod Status - red/green
Logic Status - red/green
Auxiliary Power - green
Point LED - yellow/orange/red
Communication Rate
• 125Kbps @ 500 meters (1600 feet) for
thick cable, flat media length 375 meters
(1230 feet)
• 250Kbps @ 200 meters (600 feet) for thick
cable, flat media length 150 meters (492
feet)
• 500Kbps @ 100 meters (330 feet) for thick
cable, flat media length 75 meters (246
feet)
DeviceNet Power: Voltage
Current
25V dc max
75mA
11V dc min
150mA
Auxiliary Power: Voltage
Current
30V dc
4A
10V dc
4A
Dimensions (assembled to base)
inches - (millimeters)
1.9H x 2.7W x 6.85D
(48.26)H x (68.6)W x (174)D