Rockwell-automation 1792D-8BVT8D ArmorBlock MaXum 8 Input/8 Output Mod Manuale Utente Pagina 12

  • Scaricare
  • Aggiungi ai miei manuali
  • Stampa
  • Pagina
    / 16
  • Indice
  • SEGNALIBRI
  • Valutato. / 5. Basato su recensioni clienti
Vedere la pagina 11
12 ArmorBlock MaXum 8 Input / 8 Output Module Series B
Publication 1792D-IN020B-EN-P - September 2000
Specifications
8 Input / 8 Output Module - Cat. No. 1792D-8BVT8D
Input Specifications Max. Min.
Inputs per block 8 - 3 wire or dry contact PNP or NPN devices or 4 -
4 wire PNP or NPN devices
Sensor Source Current (per
connector)
100mA total -
Off-Wire Sense Current 0.5mA -
On-state Voltage 25V dc 10V dc
On-state Current 10mA 2mA
Off-state Voltage 5V dc -
Off-state Current - 1.5mA
Output Specifications Max. Min.
Outputs per block 8 sourcing outputs labeled O0 through O7
Off Peak Blocking Voltage 30V 10V
On-state Voltage Drop 1V -
On-state Current 0.5A -
Off-state Leakage 1.5mA -
Module Current (all outputs) 4.0A -
Surge Current - for 10ms,
repeatable every 2s
2.4A -
No Load Sense Current (On-state) 0.18A -
General Specifications
Indicators Net/Mod Status - red/green
Logic Status - red/green
Auxiliary Power - green
Point LED - yellow/orange/red
Communication Rate 125Kbps @ 500 meters(1600 feet) for thick cable,
flat media length 375 meters (1230 feet)
250Kbps @ 200 meters(600 feet) for thick cable,
flat media length 150 meters (492 feet)
500Kbps @ 100 meters (330 feet) for thick cable,
flat media length 75 meters (246 feet)
DeviceNet Power Voltage
Current
Refer to the graphs in the
Overview section of the
ArmorBlock I/O Family Technical
Data, pub. no.
1792-TD001B-EN-P.
25V dc max
150mA max (no sensors)
11V dc min
up to 1.4A (8 sensors
@ 50mA per sensor)
Vedere la pagina 11