Rockwell-automation 1792D-4BVT4D ArmorBlock MaXum 4 Input/4 Output Mod Manuale Utente Pagina 11

  • Scaricare
  • Aggiungi ai miei manuali
  • Stampa
  • Pagina
    / 16
  • Indice
  • SEGNALIBRI
  • Valutato. / 5. Basato su recensioni clienti
Vedere la pagina 10
ArmorBlock MaXum 4 Input / 4 Output Module Series B 11
Publication 1792D-IN012B-EN-P - September 2000
The following table describes logic status indicators.
The following table describes auxiliary power indicators.
The following table describes I/O status indicators.
For more information on indications see the Technical Data
publication 1792-TD001B-EN-P.
Logic Status Indicators
State Status
Off Logic is disabled
Solid Green Logic is enabled
Flashing Green Local forces are applied and local logic is enabled
Auxiliary Power
Indication Status
None No Auxiliary Power
Solid Green Auxiliary Power Present
I/O Status Indicators
Function Module Status Indicator Point
Indicator
1
Condition
Outputs Green
Green
Module Status blink red
Module Status blink red
Module Status blink red
Module Status blink red
None
Yellow
Orange
Red
Orange
Red
Output not energized
Output energized
Output shorted-auto restart
Output shorted-latching
Output no load-auto restart
Output no load-latching
Inputs Green
Green
Module Status blink red
Module Status blink red
None
Yellow
Red
Blink red
No valid input
Valid input
Connector A or Connector B
short circuited
1
Connector A or Connector B
off-wire
1
1.
Only the first LED of each input connector will light as red when twin inputs are used.