ArmorBlock MaXum 4 Input / 4 Output Module with 8 Connectors, Series B 7
Publication 1792D-IN050A-EN-P - February 2001
Output Power and DeviceNet Cables
Output power and DeviceNet cables are described in the installation
publications for the cable base assembly of your choice. Refer to the
following publications:
1792D-IN009B-EN-P ArmorBlock MaXum Cable Base
Installation Guide
DN-6.7.2 DeviceNet Cable Planning and Installation Manual
Communicate With Your ArmorBlock MaXum I/O
Module
This ArmorBlock module’s I/O is exchanged with the master through
a poll, change-of-state, or cyclic connection.
The module consumes and produces I/O data as follows:
Cyclic - allows configuration of the block as an I/O client. The block
will produce and consume its I/O cyclically at the rate configured.
Polled - a master initiates communication by sending its polled I/O
message to the module. The 4 input / 4 output module consumes the
message, updates outputs, and produces a response. The response
has input data, input faults, output faults, and the status of the
Auxiliary power.
Change-of-State - productions occur when an input changes or a
fault condition occurs. If no input or fault condition change occurs
within the expected packet rate, a heartbeat production occurs. This
heartbeat production tells the scanner module that the I/O module is
alive and ready to communicate. Consumption occurs when data
changes and the master produces new output data to the I/O block.
Type of I/O Connections Consumes Produces
Cyclic 1 Byte 3 Bytes
Polled 1 Byte 3 Bytes
Change-of-State 1 Byte 3 Bytes