24 Rockwell Automation Publication 1788-UM059A-EN-P - August 2014
Chapter 3 Configure the Linking Device
6. Click Execute.
A message in the ‘Data received from device’ box indicates that the
execution was completed.
7. Click Close.
IMPORTANT
Changes to the autobaud option configuration do not take effect until
you cycle power to the linking device. You may also have to cycle power
to the slave devices.
If the linking device is the only master on the DeviceNet network, do
not enable autobaud. Automatic detection requires traffic on the
network. There is typically no traffic until a master attempts to
establish a connection.
Enable autobaud only if there are three or more devices on the
network, including the linking device.