Rockwell-automation 1788-EN2DN Ethernet-to-DeviceNet Linking Device Manuale Utente Pagina 26

  • Scaricare
  • Aggiungi ai miei manuali
  • Stampa
  • Pagina
    / 56
  • Indice
  • SEGNALIBRI
  • Valutato. / 5. Basato su recensioni clienti
Vedere la pagina 25
26 Ethernet-to-DeviceNet Linking Device
Rockwell Automation Publication 1788-IN055C-EN-P - September 2011
You should see a message in the Data received from device field
indicating that the execution was completed.
6. Click Close.
IMPORTANT
Changes to the autobaud option configuration do not take effect until you
cycle power to the linking device. You may also have to cycle power to the
slave devices.
If the linking device is the only master on the DeviceNet network, do not
enable autobaud. Automatic communication detection requires traffic on the
network. There is typically no traffic until the master establishes connections.
Vedere la pagina 25
1 2 ... 21 22 23 24 25 26 27 28 29 30 31 ... 55 56

Commenti su questo manuale

Nessun commento