Rockwell-automation 1769-OF8V Compact Analog Output Module Manuale Utente Pagina 16

  • Scaricare
  • Aggiungi ai miei manuali
  • Stampa
  • Pagina
    / 32
  • Indice
  • SEGNALIBRI
  • Valutato. / 5. Basato su recensioni clienti
Vedere la pagina 15
16 Compact 1769-OF8V Analog Output Module
Publication 1769-IN066D-EN-P - June 2010
Channel Configuration Words
The first two words of each eight word group in the configuration file allow you to change the
parameters of each channel independently. For example, words 8 and 9 correspond to channel
1 while words 56 and 57 correspond to channel 7.
Define Indicate this These bit settings
1514131211109876543210
Program
(Idle) to
Fault Enable
Program (Idle) Mode
Data Applied
(1)
(1)
These functions are not supported by all controllers (e.g. MicroLogix 1500) using any configuration method. Refer to your
controller manual for details.
0 0 0 0 0 0 0 0 0
Fault Mode Data
Applied
(1)
0 0 0 0 0 0 0 0 1
Hold for
Initialization
Disabled
0 0 0 0 0 0 0 0 0
Enabled 0 0 0 0 0 0 0 0 1
Program
(Idle) Mode
Hold Last State
(1)
0 0 0 0 0 0 0 0 0
User-Defined
Value
(1)
0 0 0 0 0 0 0 0 1
Fault Mode
Hold Last State
(1)
0 0 0 0 0 0 0 0 0
User-Defined Fault
Value
(1)
0 0 0 0 0 0 0 0 1
Enable
Ramping
Disabled 0 0 0 0 0 0 0 0 0
Enabled 0 0 0 0 0 0 0 0 1
System
Interrupt
High Clamp
Disabled 0 0 0 0 0 0 0 0 0
Enabled 0 0 0 0 0 0 0 0 1
System
Interrupt
Low Clamp
Disabled 0 0 0 0 0 0 0 00
Enabled 0 0 0 0 0 0 0 01
Enable
Channel
Disabled 0 0 0 0 0 0 0 0 0
Enabled 1 0 0 0 0 0 0 0 0
Define Indicate this These bit settings
1514131211109876543210
Output
Range
Select
-10 to +10V dc
0 0 0 0 0 0 0 0 0 0000
0 to 5V dc
0 0 0 0 0 0 0 0 0 0001
0 to 10V dc
0 0 0 0 0 0 0 0 0 0010
1 to 5V dc
0 0 0 0 0 0 0 0 0 0011
Output
Data
Select
Raw/Proportional
Counts
0 0 0 0 0 0 0 0 0 0 0 0 0
Engineering Units 0 0 0 0 00010 0 0 0 0
Scaled for PID 0 0 0 0 00100 0 0 0 0
Percent Range 0 0 0 0 00110 0 0 0 0