Rockwell-automation 1769-IF4XOF2 Compact 8-Bit Low Resolution Analog I Manuale Utente Pagina 41

  • Scaricare
  • Aggiungi ai miei manuali
  • Stampa
Vedere la pagina 40
Publication 1769-UM008A-EN-P - November 2001
Installation and Wiring 3-19
Wiring Single-ended Sensor/Transmitter Input Types
+
V in 0+
V/I in 0 -
I in 0+
V in 1+
V/I in 1-
I in 1+
V in 2+
V/I in 2-
I in 2+
ANLG Com
ANLG Com
V in 3+
I out 0+
V out 0+
I out 1 +
V out 1+
V/I in 3-
I in 3+
+
+
-
1769-IF4XOF2 Terminal Block
Sensor/
Transmitter
Power
Supply
(1)
Current
Transmitter
Signal
Voltage Transmitter
Ground Signal
(1) The sensor power supply must be rated Class 2.
(2) All analog commons (ANLG Com) are internally connected.
(3) If multiple power supplies are used, the commons must have the same ground
reference.
(4) User Belden 8761 cable (or equivalent) for wiring analog I/O.