Publication 1763-UM001D-EN-P - March 2011
Connecting to Networks via Ethernet Interface 215
Optimal Performance: RSLinx to MicroLogix 1100 Series B OS FRN4 controller
Operation Words MSG per Second Words per Second
Single Typed Read 1 50 50
Single Typed Reads 20 50 2,500
Single Typed Reads 100 50 5,000
Optimal Performance: MicroLogix 1100 Series A OS FRN3 to MicroLogix 1100
Series B OS FRN4 controller
Operation Words MSG per Second Words per Second
Single Typed Read 1 18 18
Single Typed Reads 20 18 360
Single Typed Reads 100 18 1,800
Optimal Performance: MicroLogix 1100 Series B OS FRN4 to MicroLogix 1100
Series B OS FRN4 controller
Operation Words MSG per Second Words per Second
Single Typed Read 1 20 20
Single Typed Reads 20 20 400
Single Typed Reads 100 20 2,000