Publication 1760-UM002B-EN-P - March 2005
Wiring with Pico GFX-70 4-43
6. actual value plus offset
Range A: Compare
>I1 > >I2
The actual value
>I1 increases.
The contact switches when the actual reaches the set point value.
The actual value changes and falls below the value of the set point
value minus the hysteresis.
The contact goes to the normal position.
Range B: Compare
>I1 < >I2
The actual value drops.
The contact switches if the actual reaches the set point value.
The actual value changes and rises above the value of the set point
value plus hysteresis.
The contact goes to the normal position.
Range C: Compare
>I1 > >I2 with offset
This example behaves as described in Range A. The offset value is
added to the actual value.
Comparison
>I1 = >I2
The contact switches on:
If the set point is exceeded with the actual value rising.
If the set point is undershot with the actual value decreasing.
The contact switches off:
If the hysteresis limit is exceeded with the actual value rising.
If the hysteresis limit is undershot with the actual value decreasing.
Arithmetic Function Block
Pico GFX-70 provides 32 arithmetic function blocks AR01 to AR32.
The arithmetic function block is used for arithmetic operations. All four basic
arithmetic operations are supported:
add
subtract
multiply
divide