Getting Started with ProcessLogix R500.1 9
Publication 1757-QS500A-EN-P - October 2002
Creating a Controller
The first step in configuring your hardware is to create a controller.
1. In Control Builder, select FileNewControllersCPM-Control Processor
Module.
You see the CPM Parameters dialog box (CPM = PLX52):
2. In the CPM Parameters dialog box, select the following:
IMPORTANT
Be careful to enter the CPM Parameters correctly. You will not be able to
change all of them after they are entered.
in this field: enter/select:
CPM Name CPM0101
Network Type ControlNet
Driver Name AB_PCIC-1
Supervisory MAC Address 01 (for the ControlNet 1756-CNB card)
Supervisory Slot Number 00
CPM Slot Number 01
Vedere la pagina 8