OK Indicator
Color Description Recommended Action
off No power is applied. When ready, turn on power
to the controller.
flashing
red
If the controller is: Then:
a new controller
(just
out of the box)
The controller requires a
firmware update.
See “Update the
Controller” on page 29.
NOT a new
controller
(previously in
operation)
Major fault occurred. See “Clear a Major Fault
on page 37.
solid red The controller detected a non-recoverable fault,
so it cleared the project from memory.
See “Clear a
Non-Recoverable Fault” on
page 38.
solid
green
The controller is OK None
flashing
green
The controller is storing or loading a project to or
from nonvolatile memory.
If the controller has a
CompactFlash card, leave
the card in the controller
until the OK LED turns solid
green.