Rockwell-automation 1746-NR4 SLC RTD/Resistance Input Module User Manu Manuale Utente Pagina 98

  • Scaricare
  • Aggiungi ai miei manuali
  • Stampa
Vedere la pagina 97
Publication 1746-UM008B-EN-P - December 2006
98 Ladder Programming Examples
Programming to Invoke Autocalibration
] [
Condition for
Autocalibration
I:1
1
Rung 2:0 Channel 0 Enable
B3
0
[OSR]
(U)
O:3.0
11
Channel 0 Flag
(L)
B3
1
]/[
Channel 0 Status
I:3.4
11
Rung 2:1 Channel 0 Enable
B3
1
] [
(L)
O:3.0
11
Channel 0 Flag
(U)
B3
1
Channel 0 Flag
IMPORTANT
The RTD module responds to processor commands much more
frequently than it updates its own LED indicators. Therefore, it
is normal to execute these two rungs and have the RTD module
perform an autocalibration of channel 0 without the channel 0
LED indicator ever changing state.
Vedere la pagina 97
1 2 ... 93 94 95 96 97 98 99 100 101 102 103 ... 147 148

Commenti su questo manuale

Nessun commento