Rockwell-automation 1746-HSRV SLC Servo Control Module User Manual Manuale Utente Pagina 78

  • Scaricare
  • Aggiungi ai miei manuali
  • Stampa
Vedere la pagina 77
Publication 1746-6.1.2 - July 2000
Testing Your SLC Servo Module Hardware
6-3
Testing Estop Wiring
Before you test your Estop wiring:
1. Test your fast I/O.
2. Perform open and closed loop integration of drives and
feedback devices.
A wiring diagram for the Estop circuit is shown in the following Estop
Circuitry figure. Use these connections to check the Estop Reset
push-button and each contact on the Estop string.
Figure 6.3 Estop Circuitry
To check the Estop reset push-button:
1. Uncouple the load from the motor.
2. Disconnect the drive enable contacts.
3. Disconnect the Estop string at the termination panel.
ATTENTION
!
To avoid personal injury or hardware damage,
uncouple the motor from its load.
Axis
ER
Control Module
Termination Panel
CR1
CR1
CR1
CR1
CR1
+24V
Motor
Thermal
SW
Drive
Fault
Axis
Overtravel
Remote
P2 - 9
P2 - 8
P2 - 7
P2 - 6
+24V
Estop
Estop Status
to Porcessor
Estop Reset
Request to Processor
Software
Control
Estop
Relay
Estop
Reset
P.B.
Drive Enable
Contacts
Vedere la pagina 77