Troubleshooting with the Indicators
Module Status
Off No power applied to device
Green Device operating normally
Flashing Green Device needs commissioning due to
configuration missing, incomplete or incorrect.
Flashing Red Recoverable fault.
Red Unrecoverable fault may require device
replacement
Flashing Red/Green Device is in self-test
41974
Module Status
Network Status
Status of Output 0
Status of Output 1
Output 0 NC Connection
Output 0 Relay Common
Output 0 NO Connection
+V
Output 1 NC Connection
Output 1 Relay Common
Output 1 NO Connection
+V
Relay
Output
Module
Status
Network
Status
1734
OX2
NODE:
0
1
Vedere la pagina 14
1 2 ... 10 11 12 13 14 15 16 17 18 19 20

Commenti su questo manuale

Nessun commento