POINT I/O Protected Sink Output Module 19
Publication
1734-IN585C-EN-E - December 2005
Default Data Map for the 1734-OV2E Output Module
Message size: 1 Byte
Message size: 1 Byte
Default Data Map for the 1734-OV4E Output Module
Message size: 1 Byte
Message size: 1 Byte
76543 2 1 0
Produces
(scanner Rx)
Not used Ch1 Ch0 Channel status
Where: 0 = no error, 1 = error
76543 2 1 0
Consumes
(scanner Tx)
Not used Ch1 Ch0 Channel state
Where: 0 = Off, 1 = On
76543 2 1 0
Produces
(scanner Rx)
Not used Ch3 Ch2 Ch1 Ch0 Channel
status
Where: 0 = no error, 1 = error
76543 2 1 0
Consumes
(scanner Tx)
Not used Ch3 Ch2 Ch1 Ch0 Channel
state
Where: 0 = Off, 1 = On